Source: Small Office Building Handbook
HVAC ENERGY COST SAVINGS RULES OF THUMB
BUILDING ENCLOSURE Use building insulation to minimum ASHRAE 90.1 standards.
GLAZING
If daylighting design is not contemplated, reduce cooling loads with low shading coefficient glazing. To avoid compromising the view or quality of natural light, maximize K-value.
ELECTRICAL
Any reduction in electrical loads will have corresponding cooling load reductions.
INFILTRATION
Infiltration rates of 1/2 to 1/3 air changes per hour in office buildings are a good design standard for mechanical systems. Ensure that air tightness meets this parameter.
VENTILATION
Use the lowest possible ventilation rate that still allows a healthy working environment. The advent of nonsmoking buildings may allow lower ventilation rates.
ECONOMIZER CYCLE
Investigate the addition of an economizer cycle to the ventilation system to reduce energy for cooling. When ambient conditions permit, outside air is used in lieu of the cooling plant. Ensure that continuing maintenance prevents controller drift and damper leakage above 3% or any savings will be diminished.
|